Transformer Core Ground Testing: Finding Stray Core Grounds
A transformer core is supposed to have exactly one path to ground. When a second path develops, from debris, clamps, or mechanical contact during inspection, the two grounds form a loop, and circulating currents flow through the core laminations producing heat and gases that look like a localized winding fault in DGA results.
The magnetic core of a power transformer operates at a voltage above ground potential, it is capacitively and inductively coupled to the energized windings and floats at a small fraction of winding voltage. Left entirely ungrounded, this floating voltage could build up to levels that cause intermittent discharges between the core and the grounded tank, damaging lamination insulation and producing discharge-type gases detectable in DGA. To prevent this, manufacturers provide a single, controlled core ground, typically an external connection from the core or core frame through the tank wall to the system ground, accessible from outside the tank as an isolated bushing or lead.
The word single is critical. One core ground connection prevents the floating-core discharge problem without creating any continuous current path. Two or more core ground connections create a closed magnetic loop, the flux in the core induces a voltage around the loop formed by the core itself and the external ground conductors connecting the two ground points. That induced voltage drives a circulating current around the loop. The current magnitude depends on the loop impedance, which may be low if both ground connections are solid metallic contacts. Even modest circulating currents, a few amperes, can cause localized heating of the lamination pack, degradation of the interlaminar insulation, and the generation of CO, CO2, and hydrocarbon gases that appear in DGA results.
How stray core grounds develop
Stray core grounds develop through several mechanisms, and not all of them are obvious. During factory assembly, a loose piece of metallic debris, a small bolt, a wire clip, a burr from a machined part, can become lodged between a core structure member and the tank wall or a grounded structural member inside the tank, providing a second metallic path to ground. Manufacturers inspect for this during final assembly, but it is not always caught.
Internal inspection of an in-service transformer is another common source of stray grounds. When the manhole is opened and personnel or tools enter the tank, it is easy to contact or disturb the insulation on the core frame tie rods, clamping bolts, or the core-to-frame connections in ways that create contact where there was none before. A wrench left behind is the obvious scenario, but even compressed laminations shifting under mechanical handling can create metallic contact at a point that was previously insulated.
Age-related insulation degradation on the core frame insulating material, the boards, tubes, and washers that separate the core structure from the grounded frame members, is the third mechanism. As paper insulation ages, carbonizes, and shrinks in the presence of moisture or excessive heat, its dielectric properties degrade to a point where it no longer provides adequate insulation, and what was an insulated joint becomes a conductive path. This type of stray ground often develops gradually and may produce DGA gas levels that slowly increase rather than appearing suddenly.
The core ground test procedure
The core ground test is simple and requires only a megohmmeter, a micro-ohmmeter, or a digital multimeter with a high-resistance range, depending on the fault severity. The prerequisite is that the transformer must be de-energized, isolated, and fully discharged before any connection to the core ground lead. The procedure is as follows.
First, locate the external core ground connection. On most large power transformers, this is a small insulated lead or bushing on the tank wall, labeled "core ground" or "CG," with a short pigtail or spade terminal connected to the station ground bus. On some older designs, the core ground is made through a removable link in the drain valve fitting or through an insulated bolt in the bottom of the tank. The connection method varies by manufacturer; the engineering documentation for the specific transformer must confirm the location and configuration before the test begins.
Second, disconnect the core ground lead from the station ground bus. This lifts the intentional ground connection, leaving the core electrically floating relative to the tank (which remains grounded). Now measure the resistance between the core ground terminal and the grounded tank using a megohmmeter at 500 V or 1000 V DC. If the transformer has only the single intentional core ground, lifting that ground leaves the core floating with no continuous path to the tank, the megohmmeter reading should be very high, typically greater than 100 MΩ and often above the megohmmeter's measurement range. A reading in the megohm range on a transformer with good core insulation is normal.
If a stray core ground exists, the megohmmeter will measure the resistance of the stray connection path rather than the open-circuit resistance of a properly insulated core. A low reading, tens of ohms to hundreds of kilohms depending on the nature of the stray contact, confirms that a second ground path exists. A partial insulation failure (carbonized core frame board) may read in the high megohm range but measurably below the baseline, suggesting degraded but not fully failed insulation.
After the test: reconnect before re-energization
Regardless of the test result, the core ground lead must be reconnected to the station ground bus before the transformer is re-energized. A transformer with its core ground deliberately left disconnected will float to an indeterminate voltage relative to ground, creating exactly the discharge risk the core ground was designed to prevent. It is good practice to use a torque-specified fastener at the core ground connection and to document the connection torque in the commissioning record.
If the test confirms a stray ground, the options are internal tank inspection to find and remove the source of the stray contact, continued operation with DGA trending at shortened intervals to monitor whether the stray ground is causing active heating, or removal from service for a tank entry and internal inspection. The decision depends on the magnitude of the measured resistance (lower resistance means more circulating current and more heating), the DGA picture, and the criticality of the transformer to the system. A stray ground with resistance in the kilohm range typically produces negligible circulating current and may be acceptable with monitoring; a stray ground with resistance in the single-digit ohm range is a more urgent concern.
DGA signature of a stray core ground
A stray core ground producing circulating currents through the lamination pack generates heat in the steel and its surrounding insulation. If the heat is sufficient to affect the adjacent oil or paper insulation, DGA gases will appear. The characteristic gases are carbon monoxide (CO) and carbon dioxide (CO2) from cellulose (paper) insulation degradation, and ethylene (C2H4) if steel lamination overheating reaches temperatures above approximately 300°C. The CO and CO2 profile is similar to overload-related paper aging, which can make the DGA result ambiguous without the core ground test to confirm the source.
A stray core ground that produces hydrogen (H2) and methane (CH4) without substantial CO or CO2 suggests that the heating is primarily in oil rather than paper, the stray current path is in contact with oil-immersed metal but not immediately adjacent to paper insulation. All cases of core-ground-related DGA gases warrant a core ground resistance test to confirm or rule out the stray ground as the source before other diagnostics are pursued.
Core ground test as part of the acceptance program
The core ground test is included in the standard transformer acceptance test program per NETA ATS and IEEE C57.12.90. At acceptance, a clean test result (high resistance from core ground lead to tank with lead disconnected) confirms that the factory assembled the core ground correctly and that no inadvertent grounding occurred during transport and installation. For transformers that have been de-tanked and re-tanked for transport or for internal repair, the core ground test is particularly important because re-tanking is the most common introduction point for stray grounds on previously clean units.
Southern Switch performs transformer acceptance testing including core ground testing and DGA sampling as part of commissioning programs throughout Florida and the Southeast.
Transformer Testing →Request a Quote →