Home/Learning Center/ Neutral Grounding Resistor Testing
Learning Center

Neutral Grounding Resistor Testing: Resistance, Insulation, and Thermal Capacity

A neutral grounding resistor that has drifted high in resistance limits less fault current than the protection relay expects, relay pickup thresholds calibrated to the original NGR value may no longer see a ground fault. An NGR that has drifted low lets through more current than the connected equipment was designed to withstand.

Neutral grounding resistors (NGRs) are connected between the neutral point of a medium-voltage transformer or generator and system ground to limit the current magnitude during a single-line-to-ground (SLG) fault. On an ungrounded or solidly grounded system, a SLG fault produces either uncontrolled overvoltages on the unfaulted phases (ungrounded) or very high fault current that stresses equipment and creates dangerous touch voltages (solidly grounded). An NGR provides a controlled ground path that limits fault current to a defined level while allowing protective relaying to detect and clear the fault. The resistor is the component that sets the fault current magnitude, its accuracy over time determines whether the protection system will work as designed when a fault actually occurs.

High-resistance versus low-resistance grounding

The two primary NGR applications differ substantially in resistance value and fault current limit. High-resistance grounding (HRG) systems use an NGR with resistance value equal to or greater than the capacitive reactance of the system-to-ground capacitance, limiting SLG fault current to typically 1–10 amperes. This limits fault current low enough that the system can often continue operating with a ground fault present without immediately tripping, allowing time to locate and repair the fault without a service interruption. HRG is commonly applied in industrial medium-voltage systems (2.4 kV to 15 kV) and in some generation step-up applications where continuity of service under a first ground fault is required. A 4.16 kV HRG system might have an NGR value in the range of 1,000–2,400 ohms.

Low-resistance grounding (LRG) systems use an NGR with a much lower resistance value, typically limiting SLG fault current to 100–400 amperes. This level is low enough to significantly reduce arc flash energy compared to solidly grounded systems, while being high enough to produce reliable fault current detection by conventional overcurrent ground relays (ANSI 51G or 51N). LRG is commonly applied in utility distribution substations and industrial installations where fast fault clearing is required and the higher arc energy of a solidly grounded system is unacceptable. A 13.8 kV LRG system with a 400-ampere fault current limit would have an NGR value in the range of 20 ohms.

IEEE 32 and resistance tolerance

IEEE Standard 32 (Requirements, Terminology, and Test Procedure for Neutral Grounding Devices) governs the design and testing of NGRs. IEEE 32 specifies that the resistance of a new NGR shall be within ±10% of the rated value at rated frequency and temperature. This 10% tolerance is the acceptance criterion at initial commissioning. For annual maintenance testing, field measurement that remains within ±10% of the nameplate value is generally acceptable; significant drift beyond that range warrants investigation of the resistor elements for corrosion, damage, or wrong replacement parts.

The resistance of an NGR is temperature-dependent, stainless steel and other alloy grid elements used in most NGR designs have a positive temperature coefficient, meaning resistance increases with temperature. For accuracy, resistance measurements should be taken at a known element temperature and corrected to 25°C using the appropriate temperature coefficient for the resistor material. The nameplate resistance value for most NGRs is stated at 25°C. Measuring at 40°C without correction will read approximately 5–7% high for a stainless steel element, within the IEEE 32 tolerance, but a systematic error that accumulates if never corrected.

Resistance measurement procedure

Resistance measurement of an NGR uses a precision four-wire (Kelvin) ohmmeter or a resistance bridge, connected directly to the NGR terminals. The NGR must be de-energized, isolated from the system neutral, and disconnected from the ground bus before measurement. For an LRG resistor with a 20-ohm value, a standard precision ohmmeter is adequate. For an HRG resistor with a 2,000-ohm value, a precision bridge or a calibrated decade resistance box comparison method is used to achieve the accuracy needed to detect a 10% drift. A standard digital multimeter is not sufficiently accurate for HRG resistance values at the level of accuracy required by IEEE 32.

Measurement connections go to the primary and secondary terminals of the resistor, with the four-wire connection placed to exclude the terminal contact resistance from the measurement. For a grid-type resistor where the element is a series-parallel arrangement of stainless steel ribbons, the measurement spans the full element array at the main terminals. The measured value is compared to the nameplate resistance, corrected for element temperature, and the deviation is calculated as a percentage of nameplate. Values outside ±10% trigger further investigation; values within ±5% are fully acceptable.

Insulation resistance testing

The NGR itself sits on insulated supports or in an insulated housing, for an NGR connected to the neutral of a 13.8 kV system, the resistor body is at the neutral-to-ground voltage during a fault, and the supporting structure must insulate it from the surrounding metallic enclosure. The insulation system of the NGR is tested with a megohmmeter applied between the NGR terminals (both primary and secondary connected together) and the enclosure or mounting frame.

For a typical NGR, the megohmmeter test voltage is 1000 V or 2500 V DC depending on the system voltage class. The expected result is very high insulation resistance, typically greater than 100 MΩ on a clean, dry unit. A reading below 1 MΩ indicates contamination (conductive dust, moisture, oil) on the insulator surfaces or degraded insulating material in the supports. Compromised NGR insulation means that the neutral-to-ground current path exists through the contaminated insulator even when no system fault is present, creating a parasitic ground current that confuses the ground fault detection relay and may cause spurious trips or missed faults.

Thermal inspection and element condition

An NGR carries fault current only during ground fault events. Depending on the system and its fault history, an NGR may operate rarely (once in several years) or frequently (multiple times per year in a cable-heavy industrial system with frequent insulation failures). Each operation stresses the resistor elements thermally. IEEE 32 classifies NGRs by their thermal duty: a timed-duty resistor is rated to carry fault current for a specific duration (typically 10 or 30 seconds) and must then be allowed to cool before another operation; a continuous-duty resistor is rated to carry rated current indefinitely without damage.

Physical inspection of the resistor elements focuses on corrosion, discoloration, and deformation. Stainless steel grid elements in good condition have a uniform gray or silver appearance. Elements that have been severely overloaded show discoloration ranging from dark gray to blue to black, and in extreme cases physical distortion of the ribbon material. Corroded elements, from moisture intrusion in an outdoor enclosure, or from chemicals in an industrial environment, may have a rust-colored or pitted surface. Any elements showing significant corrosion or overload damage should be replaced, as corrosion increases the element resistance and overload damage may cause loss of resistance by changing the cross-sectional area of the current path.

Connection hardware and bus inspection

The connections between the NGR and both the system neutral bus and the ground bus are points of elevated contact resistance risk. Because these connections carry current only during fault events, they may be the only electrical connections in the substation that are never warm under normal operating conditions, routine infrared thermography will never find a bad NGR connection because the connection is cool when the thermographer is present. Torque verification of the bolted connections at the neutral terminal and the ground bus connection, and inspection for corrosion or loose hardware, are necessary at each maintenance interval as a substitute for the in-service thermal check that works for every other substation connection.

Related field service

Southern Switch performs NGR testing and substation acceptance programs throughout Florida and the Southeast, including resistance measurement, insulation testing, and protection relay verification.

Acceptance Testing →Request a Quote →
Related Articles